The ISG/TM motor test cooling system is divided into two types in the industry: air-cooled and water-cooled. The working principle is to first inject a certain amount of water into the water tank in the machine, and then pass the ISG/TM motor test cooling system to cool the water. Then the low-temperature cooling water is sent to the equipment to be cooled by a water pump. The chilled water takes away the heat and then increases in temperature and returns to the water tank to achieve cooling.
Teste do motor ISG/TM Sistema de arrefecimento de alta tensão Falha de tensão e medidas de tratamento
(1). The cooling water temperature is too high and the condensation effect is poor. ISG/TM motor test cooling system has high water temperature and poor heat dissipation, which will inevitably lead to high condensing pressure. This phenomenon often occurs in high-temperature seasons. The reason for the high water temperature may be: cooling tower failure, such as the fan is not turned on or even reversed, the water distributor does not turn, it is manifested as the cooling water temperature is very high and rising rapidly; the outside temperature is high, the water path is short, and the amount of water that can be circulated In this case, the cooling water temperature is generally maintained at a relatively high level, which can be solved by increasing the storage tank.
(2) The cooling water flow rate is insufficient, and the rated water flow rate is not reached. The main performance is that the pressure difference between the inlet and outlet water of the unit becomes smaller (compared with the pressure difference at the beginning of the system’s operation), and the temperature difference becomes larger. The reason for the insufficient water flow is the lack of water in the system or the presence of air. The solution is to install an exhaust valve at the height of the pipeline to exhaust; the pipeline filter is blocked or the selection is too fine, and the water permeability is limited. You should choose a suitable filter and Clean the filter regularly; the water pump is small and does not match the system.
(3), the condenser is fouled or blocked. Condensate water generally uses tap water, which is easy to scale, and because the cooling tower is open, it is directly exposed to the air. Dust and foreign matter can easily enter the cooling water system, causing the condenser to be dirty and blocked, the heat exchange area is small, and the efficiency is low. Affect water flow. The performance is that the pressure difference and temperature difference between the inlet and outlet water of the unit become larger, and the upper and lower temperatures of the condenser are very high when the condenser is touched by hand. The unit should be backwashed regularly, and chemical cleaning and descaling should be carried out if necessary.
(4), the refrigerant is overcharged. This situation generally occurs after maintenance, and it is manifested as high suction and exhaust pressure and balance pressure, and high compressor operating current. It should be vented according to the suction and discharge pressure, balance pressure and operating current under rated conditions until normal.
(5), the refrigerant is mixed with non-condensable gases such as air and nitrogen. This situation generally occurs after maintenance, and the vacuum is not at the bottom. It can only be drained, re-evacuated, and recharged with refrigerant.
(6) False alarms caused by electrical faults. Because the high-voltage protection relay is damp, poorly contacted or damaged, the unit electronic board is damp or damaged, and the communication failure causes a false alarm. This kind of false fault, often the HP fault indicator on the electronic board is not bright or slightly bright, the high-voltage protection relay manual reset is invalid, the computer displays “HPRESET”, or disappears automatically, the running current of the compressor is normal, and the suction and discharge pressures are also normal.
Recomendações relacionadas
-
Qual é o princípio dos refrigeradores industriais arrefecidos a ar
2331Muitas produções industriais são inseparáveis do ambiente de produção a baixa temperatura fornecido pelo refrigerador e não podem obter uma capacidade de produção eficiente. Por conseguinte, o equipamento de refrigeração industrial é um equipamento de refrigeração muito importante...
Ver detalhes -
What are the advantages and disadvantages of thermal oil heating circulators?
1790The heat conduction oil heating circulator adopts a fully closed loop structure to directly act on the heat energy to the heated medium.Its advantages are: (1) Due to the continuous renewal of the heat transfer surface, the heat loss is small; (2...
Ver detalhes -
Solução para o derrame de óleo do circulador de arrefecimento e aquecimento do reator
1475When we use some reactor cooling and heating circulators, we will find that the system pressure fluctuates up and down as the temperature rises, and the oil tank is overflowing. So what are the reasons for these conditions in the cooling and heat...
Ver detalhes -
Simulação dinâmica e precisa da temperatura para bancos de ensaio na indústria automóvel
1456Os testes de qualidade e segurança são os elementos centrais do processo global de desenvolvimento e produção da indústria automóvel. Com os circuladores de arrefecimento de processos KRY-475 e 455, fornecemos aos clientes uma solução de controlo de temperatura perfeita para a...
Ver detalhes
LNEYA Refrigeradores industriais Fabricante Fornecedor