The phenomenon of ice jam in low temperature chiller system is mainly due to the excessive water in the refrigeration system. With the continuous circulation of refrigerants, the water in the refrigeration system gradually concentrates at the outlet of expansion valve. Because the outlet of expansion valve has the lowest temperature, the water turns into ice and the ice enlarges gradually. To a certain extent, the expansion valve will be completely blocked, resulting that the refrigerant can not be recycled, and the cold storage will not refrigerate.
The phenomenon of ice jam in baixo temperatura sistema de refrigeração is normal in the initial stage. There is frost in the evaporator, heat dissipation of the condenser, stable operation of the unit, clear and stable movement of refrigerant in the evaporator. With the formation of ice jam, the air flow is gradually weakened and intermittent. When the jam becomes serious, the sound of air flow completely disappears. The refrigerant cycle is interrupted. And the condenser is gradually cooled.
Because of the blockage, the exhaust pressure rises. The sound of the machine increases. There is no refrigerant flowing into the evaporator. The frost area decreases gradually. The temperature increases gradually, and the temperature of the expansion valve rises together, so the ice begins to melt. At this time, the refrigerant begins to recycle again. After a period of time, ice blockage occurs again, forming a periodic phenomenon of through-blockage.
Troubleshooting of Ice Block
The ice jam failure of low temperature chiller system is due to excessive moisture in the system, so the whole refrigeration system must be dried. There are two ways to deal with it:
1. Heat and dry the components of the refrigerant system in a drying box. Remove the compressor, condenser, evaporator, expansion valve and return pipe in the refrigerant system from the cold storage and put them into the drying box for heating and drying.
2. Remove the water content of each part of the refrigeration system by heating and secondary vacuum extraction.
Recomendações relacionadas
-
Quais são os efeitos de uma falha de energia na caixa frigorífica criogénica de azoto líquido?
1492Diferentes indústrias têm diferentes requisitos de temperatura para os crióstatos criogénicos. Naturalmente, existem muitos tipos de crióstatos criogénicos. Os métodos de refrigeração utilizados nas diferentes indústrias são diferentes. A LNEYA utiliza a refrigeração por compressor...
Ver detalhes -
A instrução do congelador de temperatura ultra baixa menos 80 graus
1771The machine must be tested before usage (or before it is energized again) in the following conditions: when ultra low temperature freezer is first used in ultra low temperature freezer minus 80 degrees, or after the ultra low temperature freezer i...
Ver detalhes -
Como substituir a válvula de quatro vias do equipamento de refrigeração industrial?
1353A válvula de quatro vias do equipamento de refrigeração industrial tem de ser substituída a tempo após um longo período de utilização, por isso, como substituí-la? Ao substituir o equipamento de refrigeração industrial, é necessário remover primeiro o tubo de ligação que liga o ...
Ver detalhes -
Discrimination of power battery integration test system
2226Using the degree of superheat to judge whether the opening degree of the integrated test system of the power battery is appropriate, and using a thermometer to measure the difference between the temperature of the return pipe and the evaporating t...
Ver detalhes
LNEYA Refrigeradores industriais Fabricante Fornecedor