A que devo prestar atenção ao substituir um compressor de chiller arrefecido a água?
Once the compressor of the water-cooled
chiller fails, the compressor needs to be replaced in time, but the replacement
of the compressor is not as simple as imagined.
Before the water-cooled chiller compressor
is replaced, the reasons for the damage to the original compressor must be
checked, and the defective parts must be replaced. Because the damage of other
parts of the water-cooled chiller will directly cause damage to the compressor.
After removing the original damaged compressor, the system must be purged with
nitrogen before the new compressor system can be connected.
During the welding operation of the
water-cooled chiller, in order not to form an oxide film on the inner wall of
the copper pipe, it is recommended to pass in nitrogen gas, and the time to
pass the nitrogen gas should be sufficient. It is forbidden to use the
compressor as a vacuum pump to empty the air in the pipeline of the external
machine when replacing the compressor or other parts, otherwise the compressor
will be burned, and a vacuum pump must be used to vacuum. When replacing, you
must add refrigerating oil that meets the nature of the compressor, and the
amount of refrigerating oil should be appropriate. Generally speaking, the new
original compressor has refrigerating oil.
When replacing the water-cooled chiller
compressor, the filter drier must be replaced in time. Because the desiccant in
the desiccant filter has been saturated and has lost the water filtering
function, clean the refrigerating oil in the original system. Because the new
pump has been injected with sufficient mass-produced refrigerated lubricating
oil, refrigerating oils of different brands cannot be mixed, otherwise it will
Deterioration causes poor lubrication, causing the compressor to pull cylinders,
turn yellow, and burn.
When replacing the compressor of a
water-cooled chiller, attention should be paid to prevent excessive
refrigerating oil in the system, otherwise the heat exchange effect of the
system will be reduced, which will increase the pressure of the system and
damage the system and the compressor. Do not fill the refrigerant too fast,
otherwise it will cause liquid shock, which will cause the valve plate to break
and cause the compressor to lose pressure.
After the compressor of the water-cooled
chiller is installed, check that the compressor is working normally, such as:
suction pressure/temperature, discharge pressure/temperature, oil pressure
differential pressure and other system parameters. If the parameter exceeds the
normal value, the reason for the abnormal system parameter must be clarified.
Recomendações relacionadas
-
What are the price factors affecting 60P freezers?
1769When users choose 60P freezers, they are very concerned about the price. Then the factors affecting the price, Wuxi Guanya (LNEYA) need to make everyone understand. The freezer brand is an important intangible asset of a company or product, and is...
Ver detalhes -
High-low temperature control system with different configurations of high-pressure reactors
1359Different configurations of high pressure reactors, the quality of products brought by different manufacturers is not the same, but the points of attention are the same, you need to pay attention to it. 1. To be used at the designated location and...
Ver detalhes -
Semiconductor refrigeration temperature control system accessories
1741In the evaporator, since the liquid evaporates in the evaporator of the semiconductor refrigeration temperature control system, the process from liquid to gas, due to the change of the load, some of the refrigerant may not be completely evaporated...
Ver detalhes -
About the size and installation height of refrigeration heating temperature control system equipment
1377Whether it is biopharmaceutical, traditional Chinese medicine or chemical pharmacy, pharmaceutical companies are all related to chemistry, because the extraction and synthesis of pharmaceutical ingredients are all in the form of chemical products...
Ver detalhes
LNEYA Refrigeradores industriais Fabricante Fornecedor