Three Common Failures Of Air Cooled Screw Chiller
Three Common Failures Of Air Cooled Screw Chiller
1. Communication Failure:
Computer controller controls various modules by telecommunication lines and total interface board, so the main cause of communication failure is poor contact or break of communication lines, especially the interface oxidation and damp of the interface. Also, the failure of unit electronic board or total interface board, incorrect choice of address dial code switch and power failure can cause the communication failure.
2. Low Voltage Failure:
The low suction pressure of the compressor results in low pressure protection relay action. The suction pressure of the compressor reflects the evaporation pressure, whose the normal value should be 0.4~ 0.6mpa, and the protection value is set to 0.2mpa. Low suction pressure causes low return air volume and insufficient cooling capacity, resulting in waste of electrical energy and the heat dissipation of the motor of gas cooled compressor which is easy to damage the motor.
3. High Voltage Failure:
High exhaust pressure of compressor results in high voltage protection relay action. The compressor exhaust pressure reflects condensation pressure whose normal value should be 1.4~ 1.6mpa, and the protection value is set to 2.0mpa. If the pressure is too high for a long time, it will cause too large of the current of compressor, which is easy to burn the motor and damage the compressor exhaust valve disc.
Recomendações relacionadas
-
Perspectivas de desenvolvimento de sistemas térmicos de ensaio eletrónico
818Para a sociedade moderna, a conservação de energia e a redução de emissões é também uma tarefa importante. No desenvolvimento de semicondutores, chips, circuitos integrados e outras indústrias, o sistema térmico de teste eletrónico pode testar eficazmente a sua temperatu...
Ver pormenores -
-
New energy vehicle battery motor test motor oil chiller and liquid chiller
1072New energy vehicle battery testing chiller
Ver pormenores -
Porque é que as empresas eléctricas necessitam de chillers industriais para sistemas de arrefecimento?
907Quando o equipamento elétrico está a funcionar no exterior, pode encontrar ambientes com temperaturas elevadas. Por exemplo, sob a luz direta do sol no verão, a temperatura pode ser muito elevada. Se o equipamento sobreaquecer, isso afectará o desempenho ou mesmo ...
Ver pormenores